Item specifications

AREA
Area covered
About 21,653m²
Office area
Approx. 177,847m²
Retail area
Approx.16,854m²
Building height
100 m
Layer number
24
Typical floor area
Approx. 4,400m²
Utility rate
70%
Parking space
1,278
FLOOR DESIGN ARRANGEMENT
Number of floors
24 floors per tower (2 towers in total: East & West Tower)
Typical office floor
17
Number of trading floors
3
Number of electromechanical floors
2
Number of retail floors
2 above ground / 1 underground
Structural loading (Office)
400kg / m²
Structural loading (Trade Floor)
500 kg / m²
Structural loading (The Core)
1,200 kg / m²
ELECTRICAL ROVISION

Dual power supply from two separate sources

Dual-power supply for each floor

Installed capacity: 25,200 KVA including 10,000 KVA (4 x 2,500 KVA transformers) for office floors and trading floors

Load distribution: 100 VA/m² for typical office floors and 140 VA/m² for trading floors

Emergency power supply

AIR-CONDITIONING LOCAL

VAV system.

24-hour chilled water supply

Fresh air supply rate at 40m³/p/hour for a typical office floor

CROSS BUILDING STANDARD

Metal ceiling system

Lamp panel

VAV air conditioning system

Elevated floor

Fire control system (automatic spraying)

Smoke detector

The layout of the main air supply pipe is installed by following the open office layout